2406J-E13TAG Electric Power Diesel Engine

Electric Power Generation 2406J-E13TAG3

Request Consultation Find your Distributor

Key Specs

Gross Mechanical Output
362-426 kWm
362-426 kWm
Typical Electrical Output
410-474 kVA (328-379 kWe)
410-474 kVA (328-379 kWe)
Emissions
EU Stage V/U.S. EPA Tier 4 Final
EU Stage V/U.S. EPA Tier 4 Final

Overview

The Perkins® 2000 Series is a family of well-proven 6 cylinder 13, 15, and 18 litre diesel engines, designed to address today’s uncompromising demands within the power generation industry.
The 2000 Series is engineered to provide outstanding performance and maximise competitive advantage for our customers.
Developed on a latest generation 12.5 litre core, the 2406 offers greater capability and more flexibility to our customers from a simple plug and play product.

Product Specifications for 2406J-E13TAG3

Gross Mechanical Output 362-426 kWm 362-426 kWm
Typical Electrical Output 410-474 kVA (328-379 kWe) 410-474 kVA (328-379 kWe)
Rated Speed 1500/1800 rpm 1500/1800 rpm
Emissions EU Stage V/U.S. EPA Tier 4 Final EU Stage V/U.S. EPA Tier 4 Final
Prime 410 KVA 410 KVA
Standby 452 kVA 452 kVA
Prime 342 kWe 342 kWe
Standby 379 kWe 379 kWe
Number of Cylinders 6 vertical inline 6 vertical inline
Bore 5.1 in 130 mm
Stroke 6.2 in 157 mm
Displacement 762.8 in³ 12.5 l
Compression Ratio 15.8:1 15.8:1
Aspiration Turbocharged aftercooled Turbocharged aftercooled
Combustion System Direct injection Direct injection
Rotation from Flywheel End Anti-clockwise Anti-clockwise
Cooling System Liquid Liquid
Aftertreatment DOC+DPF+SCR+AMOX+DEF DOC+DPF+SCR+AMOX+DEF
Switchable Yes Yes
Length 77 in 1957 mm
Width 47 in 1207 mm
Height 72 in 1837 mm
Dry Weight 4178 lb 1895 kg
Note 1 *Final dimensions dependent on selected options *Final dimensions dependent on selected options
Note 2 *Generator powers are typical and based on typical alternator efficiencies and a power factor (cos ?) or 0.8 *Generator powers are typical and based on typical alternator efficiencies and a power factor (cos ?) or 0.8
Prime Power Power available at variable load in lieu of a main power network. Overload of 10% is permitted for one hour in every 12 hours of operation. Power available at variable load in lieu of a main power network. Overload of 10% is permitted for one hour in every 12 hours of operation.
Standby Power Power available at variable load in the event of a main power network failure. No overload is permitted Power available at variable load in the event of a main power network failure. No overload is permitted

2406J-E13TAG3 Standard Equipment

Air inlet system

  • Engine mounted air filter

Cooling system

  • Radiator fitted
  • Fan
  • Fan Guard

Electrical equipment

  • ECM mounted on engine with wiring looms and sensors
  • Wiring harness (all connectors to single customer interface)
  • Starter motor
  • Battery charging alternator

Flywheels and flywheel housing

  • Flywheel
  • Flywheel housing

Fuel system

  • Engine mounted fuel filter
  • Manual fuel priming pump

Oil system

  • Temperature and oil pressure for automatic stop/alarm configurable

See how 2406J-E13TAG3 compares against frequently compared products.