Total Power Range
Gross Mechanical Output | 42 - 70 kWm 42 - 70 kWm |
Typical Electrical Output | 45-75 kVA (36-60 kWe) 45-75 kVA (36-60 kWe) |
Rated Speed | 1500/1800 rpm 1500/1800 rpm |
Key Specs
Our 1103 range of electric power engines provides cost effective power solutions for prime and standby generation. The engines also meet up to EU Stage IIIA/U.S. EPA Tier 3 equivalent emission standards. The compact 3 cylinder, 3.3 litre engines feature exceptional performance criteria in fuel economy for prime power applications and high load acceptance for standby installations.
Gross Mechanical Output | 42 - 70 kWm 42 - 70 kWm |
Typical Electrical Output | 45-75 kVA (36-60 kWe) 45-75 kVA (36-60 kWe) |
Rated Speed | 1500/1800 rpm 1500/1800 rpm |
Prime | 45 - 60 kVA 45 - 60 kVA |
Standby | 50 - 66 kVA 50 - 66 kVA |
Prime | 43 - 55 kWe 43 - 55 kWe |
Standby | 47- 60 kWe 47- 60 kWe |
Emissions | Fuel Optimised Fuel Optimised |
Number of Cylinders | 3 vertical inline 3 vertical inline |
Bore | 4.13 in 105 mm |
Stroke | 5 in 127 mm |
Displacement | 201 in³ 3.3 l |
Compression Ratio | 17.3:1 17.3:1 |
Aspiration | Turbocharged Turbocharged |
Combustion System | Direct injection Direct injection |
Rotation from Flywheel End | Anti-clockwise Anti-clockwise |
Cooling System | Liquid Liquid |
Aftertreatment | - - |
Typical Alternator Efficiency | 89% 89% |
Switchable | Yes Yes |
Length | 45.3 in 1150 mm |
Width | 30 in 760 mm |
Height | 51.2 in 1300 mm |
Dry Weight | 926 lb 420 kg |
Note 1 | *Final dimensions dependent on selected options *Final dimensions dependent on selected options |
Prime Power | Unlimited hours usage with an average load factor of 80% of the published prime power over each 24 hour period. A 10% overload is available for 1 hour in every 12 hours of operation. Unlimited hours usage with an average load factor of 80% of the published prime power over each 24 hour period. A 10% overload is available for 1 hour in every 12 hours of operation. |
Standby Power | Limited to 500 hours annual usage, up to 300 hours of which may be continuous running. No overload is permitted. Limited to 500 hours annual usage, up to 300 hours of which may be continuous running. No overload is permitted. |
Perkins product brochures and other informational documents are available for your growing business.