Total Power Range
Gross Mechanical Output | 140-204 kWm 140-204 kWm |
Typical Electrical Output | 150-220 kVA (120-176 kWe) 150-220 kVA (120-176 kWe) |
Rated Speed | 1500/1800 rpm 1500/1800 rpm |
Key Specs
The 6 cylinder, 7 litre Perkins 1106 range of ElectropaK engines gives you all the power you need for electric power generation. The engines in the range share a common platform with the option of mechanical and common rail fuel systems enabling use of the same platform over different emissions territories. Reliable, dependable and with a low cost of ownership, the engines can cope with variations in fuel quality that occur in different parts of the world.
Gross Mechanical Output | 140-204 kWm 140-204 kWm |
Typical Electrical Output | 150-220 kVA (120-176 kWe) 150-220 kVA (120-176 kWe) |
Rated Speed | 1500/1800 rpm 1500/1800 rpm |
Emissions | Fuel Optimised Fuel Optimised |
Prime | 150.0-200 kVA 150.0-200 kVA |
Standby | 165.0-220 kVA 165.0-220 kVA |
Prime | 132.0-156.8 kWe 132.0-156.8 kWe |
Standby | 146.5-173 kWe 146.5-173 kWe |
Number of Cylinders | 6 vertical inline 6 vertical inline |
Bore | 4.13 in 105 mm |
Stroke | 5.3 in 135 mm |
Displacement | 428 in³ 7.01 l |
Compression Ratio | 16:1-18.2:1 16:1-18.2:1 |
Aspiration | Turbocharged aftercooled Turbocharged aftercooled |
Combustion System | Direct injection Direct injection |
Rotation from Flywheel End | Anti-clockwise Anti-clockwise |
Cooling System | Liquid Liquid |
Aftertreatment | - - |
Typical Alternator Efficiency | 91-92% 91-92% |
Switchable | Yes Yes |
Length | 67.2 in 1706 mm |
Width | 29.8 in 756 mm |
Height | 43 in 1092 mm |
Dry Weight | 1638 lb 743 kg |
Note 1 | *Final dimensions dependent on selected options *Final dimensions dependent on selected options |
Prime Power | Unlimited hours usage, with an average load factor of 80% over each 24 hour period. A 10% overload is available for 1 hour in every 12 hours operation. Unlimited hours usage, with an average load factor of 80% over each 24 hour period. A 10% overload is available for 1 hour in every 12 hours operation. |
Standby Power | Limited to 500 hours annual usage, with an average load factor of 80% of the published standby power rating over each 24 hour period. Up to 300 hours of annual usage may be run continuously. No overload is permitted on standby power. Limited to 500 hours annual usage, with an average load factor of 80% of the published standby power rating over each 24 hour period. Up to 300 hours of annual usage may be run continuously. No overload is permitted on standby power. |