Total Power Range
Gross Mechanical Output | 192-358 kWm 192-358 kWm |
Typical Electrical Output | 207-389 kVA (166-312 kWe) 207-389 kVA (166-312 kWe) |
Rated Speed | 1500/1800 rpm 1500/1800 rpm |
The Perkins 1500 Series gives electric power customers the perfect balance of low ownership costs, world-class power density and dependable performance. With a proven, validated core, robust fuel system and excellent capability at altitude and in intense heat, these engines provide an ideal solution for customers operating in tough climate conditions in unregulated territories.
Gross Mechanical Output | 192-358 kWm 192-358 kWm |
Typical Electrical Output | 207-389 kVA (166-312 kWe) 207-389 kVA (166-312 kWe) |
Rated Speed | 1500/1800 rpm 1500/1800 rpm |
Prime | 207-308 kVA 207-308 kVA |
Standby | 228-337 kVA 228-337 kVA |
Prime | 198-282 kWe 198-282 kWe |
Standby | 218-312 kWe 218-312 kWe |
Emissions | Fuel Optimised Fuel Optimised |
Number of Cylinders | 6 vertical inline 6 vertical inline |
Bore | 4.4 in 112 mm |
Stroke | 5.9 in 149 mm |
Displacement | 537 in³ 8.8 l |
Compression Ratio | 16.1:1 16.1:1 |
Aspiration | Turbocharged aftercooled Turbocharged aftercooled |
Combustion System | Direct injection Direct injection |
Rotation from Flywheel End | Anti-clockwise Anti-clockwise |
Cooling System | Liquid Liquid |
Aftertreatment | - - |
Typical Alternator Efficiency | 92% 92% |
Switchable | Yes Yes |
Length | 76.4 in 1941 mm |
Width | 39.9 in 1013 mm |
Height | 53.8 in 1366 mm |
Dry Weight | 2549 lb 1156 kg |
Note 1 | *Final dimensions dependent on selected options *Final dimensions dependent on selected options |
Prime Power | Variable load. Unlimited hours usage with an average load of 70% of the published prime power rating. A 10% overload is available for 1 hour in every 12 hours of operation. Variable load. Unlimited hours usage with an average load of 70% of the published prime power rating. A 10% overload is available for 1 hour in every 12 hours of operation. |
Standby Power | Variable load. Limited to 500 hours annual usage up to 300 hours of which may be continuous running. No overload is permitted. Variable load. Limited to 500 hours annual usage up to 300 hours of which may be continuous running. No overload is permitted. |